top of page
The technician changed the engine oil of the power generator..jpg

What's included in your predictive maintenance?

Here's some of what we do during a basic maintenance plan (we have more detailed plans available, including our renowned Reliability Forecasting- contact us for a consultation to learn more):  

*Engine Lubrication System:

Visually check for leaks; change lube oil and filters every 12 months or 250 operating hours, whichever occurs first.

*Engine Air Cleaners:

Wet type, clean and change oil once a year; dry type, clean or replace filter, if needed. Check air flow during operation to ensure ideal performance at critical operation.

*Ignition System:

check ICM (Ignition Control Module), spark plugs, distributor, coils, magneto; set timing, if needed. Replace spark plugs as needed. Record firing and check for hotspots to ensure reliability during critical operation.

*Governor:

Check speed, sensitivity, and oil level, if applicable. Set and adjust if needed. Graphical readings are taken to ensure stability and reliability during critical operation.

*Engine Cooling System:

Check general condition; check antifreeze and add, if needed; check belts and hoses; check water pump for leaks, cavitation, and hotspots; check thermostats at operating temperature to ensure complete operation. Check flow rate to ensure reliability during critical operation.

*Engine Electric System:

Hydrometer and/or impedance test of battery; clean and lubricate battery posts and cables, load test batteries, check alternator belts; check battery alternator and charger for proper operation and adjust charger, if needed.

*Engine Fuel System:

Visually check for leaks; check all visible connections and flexible hoses; adjust carburetor; change fuel filters once a year with oil change or as needed; clean fuel strainers; replace flexible fuel hoses, if needed; check for water in day fuel tank and main fuel tank; check fuel quality and flow to ensure reliability in critical operation.

*Engine Exhaust System:

Visually check for leaks or corrosion; check condensation trap and muffler condition. Check operation and hotspots/restrictions to reduce failure during critical operation.

*AC Generator:

Visually inspect generator condition; if applicable, check slip rings and commutator for wear; check lubrication of rear generator bearing and clearances, check resistance on exciter field. Check for voltage imbalances, hotspots or any other issues that may cause failures during critical operation.

*Miscellaneous:

Check all instruments for proper operation; check timers and relays for proper operation; check all connections for tightness; check safety circuits, shutdowns, and alarm systems.

*ATS

Clean and lubricate as necessary and possible; Check wiring and contacts; Thermographic Scanning for hotspots; Check timers and controls, if allowed.

*Operation:

Run engine loaded, if permissible; at customers request and in his presence, transfer loads to generator set and adjust, if needed, to ensure accuracy and stability of entire system for operation during critical times.

*Clean Up:

Wipe down unit; remove used fluids and materials from Customer’s location and dispose of them in accordance with EPA regulations.

*Reporting

Powersmith will provide the most detailed report in the industry with any concerns and recommendations to ensure reliability of equipment.

If you're interested in learning more about our industry leading predictive maintenance,

click the "get in touch" link or call 214-888-8170

¿Ofrecen capacitación al cliente?

Sí.

Powersmith cuenta con el mejor equipo del sector y utilizamos ese equipo para brindar capacitación en el lugar a nuestros clientes. Queremos que esté bien informado para ayudarlo a tomar decisiones informadas sobre sus necesidades de energía de respaldo.

Solicita una consulta y conoce lo que podemos hacer por ti.

¿Por qué debería elegir Powersmith sobre la competencia ?

Respuesta simple: trabajamos más duro

Trabajamos más duro para usted capacitando a nuestro personal a nuestro cargo, no al suyo. Powersmith es la ÚNICA empresa con técnicos 100 % certificados. Nuestros competidores no pueden decir eso. ¿Sabía que otras empresas tienen técnicos clasificados como técnicos de mantenimiento preventivo? ¿Qué significa eso para usted? Estos técnicos no están completamente capacitados para trabajar en su equipo, no están certificados por EGSA y pueden cometer errores fácilmente, errores que pueden costarle caro. En pocas palabras, no son lo suficientemente buenos para usted. Los técnicos de Powersmith son verdaderos técnicos de generadores que están certificados por EGSA y calificados para trabajar en cada parte de su sistema de energía de respaldo. ¿Por qué confiar algo tan valioso a alguien que puede tener una capacitación limitada? ¡SIEMPRE puede confiar en Powersmith! ¡Trabajamos más duro para usted!

¿No encontraste la respuesta que buscabas?

bottom of page